Technical data

2.2

Ratings

Type

Power

[kW]

Mains

Output Current

Voltage, frequency

Current

[A]

I

r

I

max

for 60 s

[A]

(1)

[A]

(2)

[A]

(1)

[A]

(2)

ESMD251X2SFA

0.25

1/N/PE 230/240 V

2/PE 230/240 V

(180 V - 0% … 264 V + 0 %)

50/60 Hz

(48 Hz - 0 % … 62 Hz + 0 %)

3.4

1.7

1.6

2.6

2.4

ESMD371X2SFA

0.37

5.0

2.4

2.2

3.6

3.3

ESMD551X2SFA

0.55

6.0

3.0

2.8

4.5

4.2

ESMD751X2SFA

0.75

9.0

4.0

3.7

6.0

5.5

ESMD152X2SFA

1.5

14.0

7.0

6.4

10.5

9.6

ESMD222X2SFA

2.2

21.0

9.5

8.7

14.3

13.1

ESMD371X2TXA

0.37

3/PE 230/240 V

(180 V - 0% … 264 V + 0 %)

50/60 Hz

(48 Hz - 0 % … 62 Hz + 0 %)

2.7

2.4

2.2

3.6

3.3

ESMD751X2TXA

0.75

5.1

4.2

3.9

6.3

5.9

ESMD112X2TXA

1.1

6.9

6.0

5.5

9.0

8.3

ESMD152X2TXA

1.5

7.9

7.0

6.4

10.5

9.6

ESMD222X2TXA

2.2

11.0

9.6

8.8

14.4

13.2

ESMD302X2TXA

3.0

13.5

12.0

11.0

18.0

16.5

ESMD402X2TXA

4.0

17.1

15.2

14.0

22.8

21.0

(1) For rated mains voltage and carrier frequencies 4, 6, 8 kHz

(2) For rated mains voltage and carrier frequency 10 kHz

Advertising