2 troubleshooting and fault elimination, 1 controller is inhibited, Troubleshooting and fault elimination – Lenze EMF2133IB User Manual
Page 113: Controller is inhibited, Diagnostics
Advertising

Diagnostics
Troubleshooting and fault elimination
Controller is inhibited
l
113
EDSMF2133IB EN 5.0
9.2
Troubleshooting and fault elimination
9.2.1
Controller is inhibited
The controller cannot be enabled via PROFIBUS process data, i.e. the status "OPERATION
ENABLED" is not reached.
PROFIBUS
initialisation
OK?
Check
PROFIBUS
Check 2133
communication
module
Is the yellow
LED (bus) blinking?
82XX / 8200 vector:
Set the operating mode (C0001) to
3 (save parameters (C0003) if
necessary)
PIW1 =
xxxx xxxx x100 0000
bin
(switch−on inhibit)?
PIW1 =
xxxx xxxx 0xxx 1000
bin
(fault)?
Reset
fault (TRIP)
1
Select POW1 = 0000
hex
No
Yes
No
Yes
Yes