Commissioning

Configuring the host system (master)

6

l

36

EDSMF2133IB EN 5.0

Defining the user data length

The user data length is defined during the initialisation phase (configuration). Up to 12
process data words can be configured (depending on the basic device used).

Optionally you can activate the parameter data channel. If the parameter data channel is
active, it additionally occupies 4 words of the process data inputs and outputs.

ƒ

PIW: Process data input word (process data from the controller to the master)

ƒ

POW: Process data output word (process data from the master to the controller)

The user data lengths for process input data and process output data are identical. The
selection takes place via identification bytes in the configuration software for the
PROFIBUS system.

Parameter data channel

Process data channel

Without /
with

Identification / user data length

Identification / user data length

Without

l

Identification
– without consistency: 70

hex

... 7B

hex

(112 ... 123)

– with consistency: F0

hex

... FB

hex

(240 ... 251)

l

User data length: 1 ... 12 words
(PAW1/PEW1 ... PAW12/PEW12)

With

l

Identification
– without consistency: 73

hex

(115)

– with consistency: F3

hex

(243)

l

User data length: 4 words
(Word rt 1 ... word 4)

l

Identification
– without consistency: 70

hex

... 7B

hex

(112 ... 123)

– with consistency: F0

hex

... FB

hex

(240 ... 251)

l

User data length: 1 ... 12 words
(PAW1/PEW1 ... PAW12/PEW12)

General structure of the identification byte

MSB

LSB

7

6

5

4

3

2

1

0

User data length

00 1 byte or 1 word

...

15 16 bytes or 16 words

Input/Output

00 Specific identification format
01 Input
10 Output
11 Input and output

Length/Format

0 Byte
1 Word

Consistency

0 Byte or word
1 Total length