Parameter data transfer

Lenze parameter sets
Parameter sets for 8200 vector controller

8

l

84

EDSMF2133IB EN 5.0

8.1.2

Parameter sets for 8200 vector controller

The 8200 vector controller has four parameter sets the parameters of which can be directly
addressed via the bus.

Addressing

Addressing is carried out with a code offset:

ƒ

Offset "0" addresses parameter set 1 with codes C0000 ... C1999.

ƒ

Offset "2000" addresses parameter set 2 with codes C2000 ... C3999.

ƒ

Offset "4000" addresses parameter set 3 with codes C4000 ... C5999.

ƒ

Offset "6000" addresses parameter set 4 with codes C6000 ... C7999.

If a parameter is only available once (see documentation of the controller), use code offset
"0".

Example

Addressing of code C0011 (maximum field frequency) in different parameter sets:

ƒ

C0011 in parameter set 1: code number = 11

ƒ

C0011 in parameter set 2: code number = 2011

ƒ

C0011 in parameter set 3: code number = 4011

ƒ

C0011 in parameter set 4: code number = 6011

)

Note!

Automatic storage of new parameter data is activated (basic Lenze setting, can
be deactivated via C0003).