4electrical installation – Lenze E82ZAFVC001_ User Manual

Page 42

Advertising
background image

4

Electrical installation

EDK82ZAFVC001 DE/EN/FR 2.0

42

l

M5 Kabelspezifikation−innenschaltung

Specification of the transmission cable

The devices are connected to the bus system using a fieldbus cable according to the
DeviceNet

TM

specification (DeviceNet Adaption of CIP, Edition 1.1, Volume Three).

Companies like Belden Wire & Cable, Olflex Wire & Cable, C&M Corp. and Madison Cable
produce DeviceNet

TM

Thick" and Thin" cables.

)

Note!

Use the Thin" cable to wire the function module

^ 42

.

Features of the Thin" cable according to DeviceNet specifications

General features

Configuration

Two shielded symmetrical cables with a common axis and drain wire in
the centre

Total shielding

65% coverage
AWG 36 or min. 0.12 mm tinned braid (individually tinned)

Drain wire

Copper 22 min.; min. 19 cores (individually tinned)

Outer diameter

6.096 mm (min.) to 7.112 mm (max.)

Roundness

Radius deviation must be within 20% of 0.5 outer diameter

Jacket marking

Vendor name & part no. and additional markings

Spec. DC resistor (braid, tape, drain)

10.5 Ohm/1000 m (nominal at 20°C)

Certifications (U.S. and Canada)

NEC (UL), CL2 (min.)

Bend radius

20 x diameter (installation) / 7 x diameter (fixed)

Ambient operating temperature

−20°C to +70°C at 1.5 Ampere; derate current linearly to zero at 80°C

Storage temperature

−40°C to +85°C

Pull tension

289.23 N

max