Setting options via switches, 5commissioning – Lenze E82ZAFVC001_ User Manual

Page 50

Advertising
background image

5

Commissioning

Setting options via switches

EDK82ZAFVC001 DE/EN/FR 2.0

50

l

H1inbet−reihenfolge einhalten

Setting options via switches

)

Note!

Settings via GDC, operating module or configuration software

The settings of device address and baud rate via GDC, the operating module or
the configuration software only become valid when the DIP switches S7 and S8
are in the "ON" position.

Settings via front switch

The Lenze setting of all switches is OFF.

The device address and baud rate set via DIP switch will only be active after a
renewed mains connection.

The switch S9 is ineffective.

The following settings can be easily carried out via the front DIP switch of the function
module:

ƒ Software compatibility of E82ZAFVC / E82ZAFD function module with S10

ƒ Device address with S1 − S6

ƒ Baud rate with S7 / S8

ON

1

6

2

7

4

3

8

5

9 10

ON

OFF

E82ZAFD005

Fig. 1

Software compatibility setting

Compatibility

S10

E82ZAFVC0xx

OFF

E82ZAFD
For the description of the
function module see the
E82ZAFD Mounting Instructions

ON