Commissioning

5

EDK82ZAFVC001 DE/EN/FR 2.0

55

l

inbetrieb−statusanzeige AFV0xx

see

Procedure

Step

8.

Configure process data channel of the standard device (see "application
range") for operation with the function module.

Recommendation
Set code C0005 = 200 after the Lenze setting has been loaded (C0002).
C0005 = 200 preconfigures the device for the operation with a function
module. Control and status words are already linked.

Continue with step 12.

Manual of
the standard
device

9.

If required, assign the process output data of the master/scanner via
C1511 to the input signals of the standard device.

^ 38

10.

If required, assign the process input words of the master/scanner to the
output signals of the standard device via C1510.

^ 38

11.

If the configuration in step 9. or step 10. has been changed:
Enable process output data with C1512 = 65535.

^ 38

12.

Enable standard device with terminal 28 (CINH) (terminal 28 on HIGH).

13.

Send setpoint via a selected process data output word.
The drive is now running.

14.

Inhibit the standard device via the bus (e.g. control word bit 9) or terminal
28 (CINH).

Protection against uncontrolled restart

)

Note!

In some cases the controller should not restart after a fault (e.g. after a short
mains failure).

ƒ

The drive can be inhibited by setting C0142 = 0 if
– the corresponding controller sets a fault "LU message" and
– the fault is active for more than 0.5 seconds.

Parameter function:

ƒ

C0142 = 0
– The controller remains inhibited even after the fault has been

eliminated and

– the drive restarts in a controlled mode: LOW−HIGH transition at terminal

28 (CINH)

ƒ

C0142 = 1
– An uncontrolled restart of the controller is possible.