5

Commissioning

EDK82ZAFVC001 DE/EN/FR 2.0

54

l

inbetrieb−statusanzeige AFV0xx

Step

Procedure

see

1.

If necessary, set the software compatibility

^ 50

2.

Set the node address

3.

Set the baud rate

4.

Inhibit the standard device via terminal 28 (CINH).

Terminal 28 on LOW potential.
The standard device can be inhibited and enabled via the bus

Manual of
the standard
device

5.

Connect mains voltage

6.

Connect the separate voltage supply for the function module
(Switch on the DeviceNet).

^ 44

Response of the front LED display:
Directly after the voltage supply for the function module has been
connected, both LEDs at the front light up for a short time in the following
order:

l

The LED Status of connection with bus" changes its colour from green
to red before it goes off.

l

The LED "Status of the connection to the standard device" changes its
colour from green to red before it goes off.

l

The LED Connection status to the bus" at the front of the function
module is blinking (only visible in case of 8200 vector).

l

The green LED Status of connection with standard device" at the front
of the function module is on (only visible in case of 8200 vector).

l

Keypad:

dc

(if attached)

^ 56

7.

Configure the host system for communicating with the function module
with configuration software:

l

With explicit messages" all parameters can be read or written from
the drive and/or function module.

l

Actual values can be read (e.g. status word) or setpoints can be written
(e.g. frequency setpoint) via the I/O data.

Response

l

The LED Status of connection with the bus" at the front of the
function module changes from blinking to the constantly ON state.