4electrical installation – Lenze E82ZAFVC001_ User Manual

Page 48

Advertising
background image

4

Electrical installation

EDK82ZAFVC001 DE/EN/FR 2.0

48

l

merker_ueb−busltgslaenge

Max. possible bus cable length

The following bus cable lengths are possible in dependence on the baud rate and the cable
used:

Baud rate

Thin Cable

Thick Cable

125 kbits/s

100 m

500 m

250 kbits/s

250 m

500 kbits/s

100 m

When using both, Thick" and Thin" cables, the maximum cable lengths are to be selected
according to the baud rate:

Baud rate

Bus cable length

125 kbits/s

L

max

= 500 m

= L

thick

+ 5 L

thin

250 kbits/s

L

max

= 250 m

= L

thick

+ 2.5 L

thin

500 kbits/s

L

max

= 100 m

= L

thick

+ L

thin