Status display, 5commissioning – Lenze E82ZAFVC001_ User Manual
Page 56
![background image](/manuals/565929/56/background.png)
Commissioning
Status display
EDK82ZAFVC001 DE/EN/FR 2.0
56
l
inbetrieb−statusanzeige AFV0xx
Status display
E82ZAFVC001E
Pos
Colour
Status
Notes
0
OFF
Function module is not supplied with voltage,
external voltage supply is switched off
GREEN
BLINKING Function module is supplied with voltage but not connected to the
controller.
Reason:
Standard device is
l
switched off
l
is being initialised
l
not available
ON
Function module is supplied with voltage and is connected to the
standard device
RED
BLINKING Internal error, Lenze setting has been loaded
ON
Internal error of the function module
1
OFF
l
No connection to the master
l
Function module is not supplied with voltage.
GREEN
BLINKING
Dup_Mac_ID" test phase. Not yet connected to master (scanner).
ON
DeviceNet connection established.
RED
BLINKING No communication because time limit has been exceeded
ON
Critical bus error