Setting the baud rate and address, Commissioning – Lenze E82ZAFVC001_ User Manual

Page 51

Advertising
background image

Commissioning

Setting the baud rate and address

5

EDK82ZAFVC001 DE/EN/FR 2.0

51

l

H1inbet−reihenfolge einhalten

Setting the baud rate and address

Node address setting

)

Note!

The device address must be set via software, when the switches S7 and S8 are
in ON position.

In this case the switches S1 to S6 are ineffective.

ON

1

6

2

7

4

3

8

5

9 10

ON

OFF

Fig. 2

Address assignment via DIP switch

)

Note!

If several controllers are connected to the network, the node addresses must
differ from each other.

The address (decimal number) is calculated by inserting the positions of switches S1 to S6
(’0’ = OFF and ’1’ = ON) into the following equation.

Address

dec

= S6 · 2

0

+ S5 · 2

1

+ S4 · 2

2

+ S3 · 2

3

+ S2 · 2

4

+ S1 · 2

5

The equation can also be used to calculate the valency of a switch. The sum of valencies
results in the node address to be set:

Switch

Valency

Example

Switch position

Node address

S1

32

ON

32 + 16+ 8 = 56

S2

16

ON

S3

8

ON

S4

4

OFF

S5

2

OFF

S6

1

OFF