13 fault codes (dfaults register), Programming – Lenze PM94P01C User Manual

Page 58

Advertising
background image

PM94P01C

56

Programming

Table 18: Encoding for Extended Status Bits (Variable #83 EXSTATUS):

Bit #

Function

Comment

0

Reserved

1

Velocity in specified window

Velocity in limits as per parameter #59: VAR_VLIMIT_SPEEDWND

2-4

Reserved

5

Velocity at 0 (zero)

Velocity 0: Zero defined by parameter #58: VAR_VLIMIT_ZEROSPEED

6,7

Reserved

8

Bus voltage below under-voltage limit Utilized to indicate drive is operating from +24V keep alive and a valid DC

bus voltage level is not present.

9,10

Reserved

11

Regen circuit is on

Drive regeneration circuit is active. Drive will be dissipating power through
the braking resistor (if fitted).

12-20 Reserved

21

Set if homing operation in progress

Drive executing Pre-defined homing function (see section 2.15).

22

Set if system homed

Drive completed Pre-defined homing function (see section 2.15).

23

If set then last fault will remain on the
display until re-enabled.

User can set this bit to retain fault code on the display until re-enabled. It is
useful if there is a fault handler routine. When the fault handler is exited, the
fault number on the display will be replaced by current status (usually DiS if
bit #24 is not set). Setting bit #24 retains diagnostics on the display.

24

Set if EIP IO exclusive owner
connection is established. Cleared if
closed.

Checks if drive is controlled by EthernetIP master. Use bit #24 and bit #25 to
process “lost of connection” condition (if needed ) in the user’s program

25

Set if EIP IO exclusive owner
connection times out. Cleared if exc.
owner conn exsists.

Checks if connection with Ethernet/IP master is lost. Use bit #24 and bit #25
to process “lost of connection” condition (if needed) in the user’s program

26-31 Reserved

2.13 Fault Codes (DFAULTS register)

Whenever a fault occurs in the drive, a record of that fault is recorded in the Fault Register (DFAULTS). In addition,
specific flags in the System Status Register will be set helping to indicate what class of fault the current fault belongs to.
Table 19 summarizes the possible fault codes. Codes from 1 to 16 are used for DSP subsystem errors. Codes above
that range are generated by various subsystems of the PositionServo.

Table 19: DFAULTS Register

Fault

ID

Associated flags

in status register

Description

1

1, 3

Over voltage

2

1, 3

Invalid Hall sensors code

3

1, 3

Over current

4

1, 3

Over temperature

5

1, 3

The drive is disabled by the EN954-1 Safety Function

6

1, 3

Over speed. (Over speed limit set by motor capability in motor file)

7

1, 3

Position error excess.

8

1, 3

Attempt to enable while motor data array invalid or motor was not selected.

9

1,3

Motor over temperature switch activated

10

1,3

Sub processor error

11-13

-

Reserved

14

1,3

Under voltage

15

1,3

Hardware current trip protection

16

-

Reserved

17

3

Unrecoverable error.

18

16

Division by zero

19

16

Arithmetic overflow