Homing Mode Operation example

The following steps are needed to execute the homing operation from the user program or under interface control.

1. Set Fast homing speed:

Variable #242

2. Set Slow homing speed:

Variable #243

3. Set Homing accel/decel:

Variable #239

4. Set home offset:

a. In User Units

Variable #240

b. In encoder pulses

Variable #241

5. Set Home Switch Input

Variable #246

6. Select Home Method

Variable #244

‘HOME’ is the logical command to set VAR_START_HOMING. Writing the word ‘HOME’ within the user program will
result in the homing operation commencing. After initiating the HOME command with firmware 3.60 (and later) the user
program will not execute subsequent lines of code until after homing is completed (similar to MOVE P). If either using
firmware prior to 3.60 or if user initiates homing in the indexer program via the statement VAR_START_HOMING=1,
then it is recommended to immediately follow that statement with the following code:

WAIT UNTIL VAR_EXSTATUS & 0x400000 == 0x400000.

Doing this ensures no further lines of code will be executed until homing is complete.

;Program start-------------------------------------------------------------------
;
;

UNITS=1

;rps

Accel=1000

Decel=1000

MaxV =20

;some program statements…
;
;
;Homing specific set up..

VAR_HOME_FAST_VEL=

10

;rps

VAR_HOME_SLOW_VEL=

1

;rps

VAR_HOME_ACCEL=

100

;rps/sec^2

VAR_HOME_OFFSET=

0

;no offset from sensor

VAR_HOME_SWITCH_INPUT=

4

;

input B1 (0-A1, 1-A2…3-A4,4-B1,…11-C4)

VAR_HOME_METHOD=

4

;see table 22

ENABLE

HOME

;starts homing sequence

WAIT UNTIL VAR_EXSTATUS & 0x400000 == 0x400000 ;wait for homing complete

;Drive homed

;Program statements…
END