Technical data 2.2 power ratings, 3 fuse recommendations – Lenze S94P01G Position Servo User Manual

Page 12

Advertising
background image

S94P01G

10

Technical Data

2.2

Power Ratings

Type

(1)

Output kVA at

Rated Output

Current (8kHz)

(2)

Leakage Current

Power Loss at

Rated Output

Current

(8kHz)

Power Loss at

Rated Output

Current

(16 kHz)

(3)

Units

kVA

mA

Watts

Watts

E94_020S1N_X

0.8

Typically >3.5 mA.

Consult factory for

applications requiring

<3.5 mA.

19

21

E94_040S1N_X

1.7

29

30

E94_020S2F_X

0.8

19

21

E94_040S2F_X

1.7

29

30

E94_080S2F_X

3.3

61

63

E94_100S2F_X

4.2

80

85

E94_020Y2N_X

0.8

19

21

E94_040Y2N_X

1.7

29

30

E94_080Y2N_X

3.3

61

63

E94_120Y2~_X

5.0

114

129

E94_180T2~_X

7.5

171

195

E94_020T4N_X

1.7

31

41

E94_040T4N_X

3.3

50

73

E94_050T4N_X

4.2

70

90

E94_060T4~_X

5.0

93

122

E94_090T4~_X

7.5

138

182

2.3

Fuse Recommendations

Type

(1)

AC Line

Input Fuse

(1ш/3ш)

Miniature

Circuit Breaker

(6)

(1ш/3ш)

AC Line Input

Fuse

(4)

or

Breaker

(5)

(N. America)

DC Bus Input

Fuse

(7)

Amp Ratings

E94_020S1N_X

M20/M10

C20/C10

20/10

10

E94_040S1N_X

M32/M20

C32/C20

30/20

20

E94_020S2F_X

M20

C20

20

15

E94_040S2F_X

M20

C20

20

20

E94_080S2F_X

M32

C32

32

40

E94_100S2F_X

M40

C40

40

45

E94_020Y2N_X

M20/M16

C20/C16

20/15

15

E94_040Y2N_X

M20/M16

C20/C16

20/15

20

E94_080Y2N_X

M32/M20

C32/C20

30/20

40

E94_120Y2~_X

M50/M32

C50/C32

50/30

55

E94_180T2~_X

M40

C40

40

80

E94_020T4N_X

M10

C10

10

10

E94_040T4N_X

M10

C10

10

20

E94_050T4N_X

M16

C16

15

25

E94_060T4~_X

M20

C20

20

30

E94_090T4~_X

M25

C25

25

40

(1)

The first “_” equals “P” for the Model 940 encoder based drive

or “R” for the Model 941 resolver based drive.

When the 10th digit is marked by “~”, “N” = No line filter

or “F” = Integrated line filter

The second “_” equals “E” for incremental encoder (must have E94P drive)

or “R” for the standard resolver (must have E94R drive).

(2)

At 240 VAC line input for drives with suffixes “S1N”, “S2F”, “Y2N”. At 480 VAC line input for drives with suffixes “T4N”.
a. The output power is calculated from the formula: output kVA = [(

3

) x U

LL

x I

rated

] / 1000

b. The actual output power (kW) depends on the motor in use due to variations in motor rated voltage, rated speed and power factor, as well as

actual max operating speed and desired overload capacity.

c.

Typical max continuous power (kW) for PM servo motors runs 50-70% of the kVA ratings listed.

(3)

At 16 kHz, de-rate continuous current by 17%

(4)

Installations with high fault current due to large supply mains may require a type D circuit breaker.

(5)

UL Class CC or T fast-acting current-limiting type fuses, 200,000 AIC, preferred. Bussman KTK-R, JJN, JJS or equivalent.

(6)

Thermal-magnetic type breakers preferred.

(7)

DC-rated fuses, rated for the applied voltage. Examples Bussman KTM or JJN as appropriate.