S94P01G

49

Parameters

5.5.2 Analog Output Current Scale (Volt / amps)

Applies scaling to all functions representing CURRENT values.

5.5.3 Analog Output Current Scale (mV/RPM)

Applies scaling to all functions representing VELOCITY values. (Note: that mV/RPM
scaling units are numerically equivalent to volts/kRPM).

5.5.4 Analog Input Dead Band

Allows the setting of a voltage window (in mV) at the reference input AIN1+ and AIN1-
(P3 pins 24 and 25) such that any voltage within that window will be treated as zero
volts. This is useful if the analog input voltage drifts resulting in motor rotation when
commanded to zero.

5.5.5 Analog Input Offset Parameter

Allows you to adjust the offset voltage at AIN1+ and AIN1- (P3 pins 24 and 25). This
function is equivalent to the balance trim potentiometer found in analog drives. Lenze
recommends that this adjustment be made automatically using the “Adjust analog
voltage offset” button while the external analog reference signal commands zero speed.

5.5.6 Adjust Analog Input Zero Offset

This control button is useful to allow the drive to automatically adjust the analog input
voltage offset. To use it, command the external reference source input at AIN1+ and
AIN1- (P3 pins 24 and 25) to zero volts and then click this button. Any offset voltage
at the analog input will be adjusted out and the adjustment value will be stored in the
“Analog input offset” parameter.

5.6

Digital I/O

The PositionServo has four digital outputs. These outputs can be either assigned to one
of the following functions, or be used by the drives internal User Program

Not Assigned

No special function assigned. Output can be used by the User Program.

Zero Speed

Output activated when drive is at zero speed, refer to “Velocity Limits”
(section 5.7) for settings.

In Speed Window Output activated when drive is in set speed window, refer to “Velocity

Limits” (section 5.7) for settings.

Current Limit

Output activated when drive detects current limit.

Run Time Fault

A fault has occurred. Refer to section 8.3 for details on faults.

Ready

Drive is enabled.

Brake

Command for the holding brake option (E94ZAHBK2) for control of a
motor with a holding brake. This output is active 10ms after the drive is
enabled and deactivates 10ms before the drive is disabled.

In position

Position mode only. Refer to the Programming Manual.

5.6.1 Digital Input De-bounce Time

Sets de-bounce time for the digital inputs to compensate for bouncing of the switch or
relay contacts. This is the time during an input transition that the signal must be stable
before it is recognized by the drive.