3 installation, 1 input voltage ratings, 2 input fusing and disconnect requirements – Lenze SCF frequency inverter User Manual

Page 16: Warning

Advertising
background image

16

Lenze 13466146 EDBSF01 v24 EN

3 Installation

3.2.1 Input Voltage Ratings

SF200 Series drives are rated for 208/240 Vac, three phase, 50-60 Hz input. The drive will function
with input voltages of 208 to 240 Vac (+ 10%, - 15%), at 48 to 62 Hz.

SF200Y Series drives are rated for 208/240 Vac, single or three phase, 50-60 Hz input. The drive will
function with input voltage of 208 to 240 Vac (+10%, -15%), at 48 to 62 Hz.

SF400 Series drives are rated for 400/480 Vac three phase, 50-60 Hz input. The drive will function
with input voltages of 400 to 480 Vac (+ 10%, - 15%), at 48 to 62 Hz.

SF500 Series drives are rated for 480/590 Vac, three phase, 50-60 Hz input, and will function with
input voltages of 480 to 590 Vac (+ 10%, - 15%), at 48 to 62 Hz.

NOTE
Parameter 01 - LINE VOLTAGE SELECTION must be programmed according to the applied
input voltage. Refer to Section 4.4 - Description of Parameters.

3.2.2 Input Fusing and Disconnect Requirements

A circuit breaker or a disconnect switch with fuses must be provided in accordance with the National
Electric Code (NEC) and all local codes. Refer to the following tables for proper fuse/circuit breaker
ratings and wire sizes.

INPUT FUSE & CIRCUIT BREAKER RATINGS

208/240 Vac, 1 phase 208/240 Vac, 3 phase

400/480 Vac, 3 phase

480/590 Vac, 3 phase

MODEL

RATING

MODEL

RATING

MODEL

RATING

MODEL

RATING

SF203Y

10 A

SF203Y

10 A

SF205Y

10 A

SF205(Y)

10 A

SF405

10 A

SF210Y

15 A

SF210(Y)

10 A

SF410

10 A

SF510

10 A

SF215Y

20 A

SF215(Y)

12 / 10 A

SF415

10 A

SF220Y

25 / 20 A

SF220(Y)

15 / 12 A

SF420

10 A

SF520

10 A

SF230Y

30 / 25 A

SF230(Y)

20 / 15 A

SF430

10 A

SF530

10 A

SF250Y

45 / 40 A

SF250(Y)

30 / 25 A

SF450

15 A

SF550

12 A

SF275

45 / 40 A

SF475

20 A

SF575

20 A

SF2100

50 / 50 A

SF4100

30 / 25 A

SF5100

20 A

SF2150

80 / 75 A

SF4150

40 / 35 A

SF5150

30 A

SF2200

100 / 90 A

SF4200

50 / 45 A

SF5200

40 A

SF4250

70 / 60 A

SF5250

45 A

SF4300

80 / 70 A

WARNING!

Per UL requirements, use a fuse (not a circuit breaker) for 240 VAC drives requiring
>40A protection and for 480 VAC & 600 VAC drives requiring >32A protection.
Additionally, use a fuse (not a circuit breaker) for the following models:SF215Y,
SF220Y, SF230Y, SF250Y, SF250, SF275, SF575, SF5100, and SF5150.