4 Commissioning

4.4

Description of Parameters

P01

LINE VOLTAGE SELECTION

This calibrates the drive for the actual applied input voltage, and can be set to HIGH (01) or LOW (02).
Refer to the table below for the proper setting depending on the input voltage.

MODEL

RATED INPUT

VOLTAGE

INPUT

PHASE

APPLIED INPUT

VOLTAGE

PARAMETER

SETTING

SF200Y

208 / 240 Vac

1 or 3

220 - 240 Vac

HIGH (01)

1 or 3

200 - 208 Vac

LOW (02)

SF200

208 / 240 Vac

3

220 - 240 Vac

HIGH (01)

3

200 - 208 Vac

LOW (02)

SF400

400 / 480 Vac

3

440 - 480 Vac

HIGH (01)

3

380 - 415 Vac

LOW (02)

SF500

480 / 590 Vac

3

575 - 600 Vac

HIGH (01)

3

460 - 480 Vac

LOW (02)

NOTE
If this parameter is changed while the drive is running, the new value will not take
effect until the drive is stopped.

P02

CARRIER FREQUENCY

This sets the switching rate of the output IGBT’s. Increasing the carrier frequency will result in less
audible motor noise. Available settings are: 4 kHz, 6 kHz, 8 kHz, and 10 kHz.

PARAMETER

SETTING

CARRIER

FREQUENCY

MAXIMUM OUTPUT

FREQUENCY (NOTE 1)

AMBIENT OR OUTPUT

DERATE (NOTE 2)

01

4 kHz

240.0 Hz (400.0 Hz)

50ºC or 100%

02

6 kHz

240.0 Hz (600.0 Hz)

50ºC or 100%

03

8 kHz

240.0 Hz (999.9 Hz)

43ºC or 92%

04

10 kHz

240.0 Hz (999.9 Hz)

35ºC or 82%

NOTE
• For drives with the High Output Frequency option, the carrier frequency also

determines the maximum output frequency (shown in parenthesis).

• The SCF drive is fully rated up to 6 kHz carrier frequency. If the 8 kHz or 10 kHz

carrier frequency is selected, the drive’s ambient temperature rating OR output
current rating must be de-rated to the value shown in the table above.

• If this parameter is changed while the drive is running, the change will not take

effect until the drive is stopped. Therefore, the allowable maximum frequency for
drives with the High Output Frequency option (see NOTE 1) will not change if the
carrier frequency is changed while the drive is running.