Installation 3 – Lenze SCF frequency inverter User Manual

Page 27

Advertising
background image

Lenze 13466146 EDBSF01 v24 EN

27

Installation 3

3.6.5 Speed Pot and Preset Speed Control

Shown below is the wiring for SPEED POT and/or PRESET SPEED control, and either a two-wire or
three-wire start/stop circuit:

1 2 5 6

12

TXA TXB

2

13A 13B 13C

14

15

2

STO

P

C

O

MM

ON

0-10 VDC

IN

PU

T

STA

RT

PR

ESET SPEED SELECT

C

O

MM

ON

11

25

31

30

10 VDC

SU

PPL

Y

2.5k - 10kΩ

PR

ESET SPEED SELECT

PR

ESET SPEED SELECT

The TB-2 terminals are internally connected to each other

NOTE

• Program the PRESET SPEEDS (Parameters 31-37) to the desired values.
• PRESET SPEED #2 (04), and TB-13C (Parameter 12) to PRESET SPEED #3 (04). To

select a preset speed, close the appropriate TB-13 terminal(s) to TB-2 (refer to
Parameters 31-37 for the Preset Speed Activation table).

• If reverse rotation is also required, TB-13A cannot be used as a PRESET SPEED

SELECT. TB-13A must be programmed to select RUN REVERSE (05) or START
REVERSE (06), leaving only TB-13B and TB-13C to select preset speeds.

• For speed pot control, program Parameter 05 - STANDARD SPEED SOURCE

for 0-10 VDC (03). If none of the preset speeds are selected (all of the TB-13
terminals are open), the drive will respond to the speed pot.