Commissioning 4

P11

TB-13B FUNCTION SELECT

This selects the function of terminal TB-13B. Closing TB-13B to TB-2 (or opening in the case of setting
08) activates the selected function. The following functions can be selected:

01

NONE: Disables the TB-13B function.

02

0-10 VDC: Selects a 0-10 VDC signal (at TB-5) as the AUTO speed reference input.

03

4-20 mA: Selects a 4-20 mA signal (at TB-25) as the AUTO speed reference input.

04

PRESET SPEED #2: Selects PRESET SPEED #2 as the AUTO speed reference. The drive will operate
at the frequency programmed into Parameter 32.

05

DECREASE FREQUENCY: Decreases the speed setpoint when using the MOP function. Refer to
Section 3.5.6.

06

JOG FORWARD: Jog in the forward direction. In this mode, the drive will JOG at the speed
programmed into Parameter 32 - PRESET SPEED #2.

07

JOG REVERSE: Jog in the reverse direction. In this mode, the drive will JOG at the speed
programmed into Parameter 32 - PRESET SPEED #2.

WARNING!
When operating in JOG mode, the STOP terminal (TB-1), the AUXILIARY STOP function
(see setting 08), and the STOP key on the optional remote keypad WILL NOT stop the
drive. To stop the drive, remove the JOG command.

JOG REVERSE will operate the drive in reverse rotation even if ROTATION DIRECTION
(Parameter 17) is set to FORWARD ONLY.

08

AUXILIARY STOP: When TB-13B is opened with respect to TB-2, the drive will decelerate to a
STOP (even if STOP METHOD is set to COAST) at the rate set into Parameter 42 - ACCEL/DECEL
#2.

NOTE
If the drive is commanded to JOG while running, the drive will enter JOG mode and
run at PRESET SPEED #2. When the JOG command is removed, the drive will STOP.