Commissioning 4 – Lenze SCF frequency inverter User Manual

Page 39

Advertising
background image

Lenze 13466146 EDBSF01 v24 EN

39

Commissioning 4

P08

TB-30 ANALOG OUTPUT

Terminal TB-30 can be used as an analog output proportional to either output frequency or load.
FREQUENCY SCALING (Parameter 40) or LOAD SCALING (Parameter 41) can be used to scale the
output signal.

01 NONE

02

0-10 VDC FREQ

03

2-10 VDC FREQ

04

0-10 VDC LOAD

05

2-10 VDC LOAD

NOTE
The 2-10 VDC signal can be converted to a 4-20 mA signal by connecting a resistor
in series with the signal such that the total load resistance is 500 Ohms. However,
this output cannot be used with devices that derive power from a 4-20 mA signal.

P09

TB-31 ANALOG OUTPUT

Terminal TB-31 can be used as an analog output proportional to load, or as the control signal to
activate the optional external Dynamic Braking module. LOAD SCALING (Parameter 41) can be used
to scale the output signal when TB-31 is used as an analog output proportional to load.

01 NONE

02

0-10 VDC LOAD

03

2-10 VDC LOAD

04

DYNAMIC BRAKING: TB-31 becomes the “trigger” that activates the optional external Dynamic
Braking module. Refer to the instructions included with the Dynamic Braking option.

NOTE
The 2-10 VDC signal can be converted to a 4-20 mA signal by connecting a resistor
in series with the signal such that the total load resistance is 500 Ohms. However,
this output cannot be used with devices that derive power from a 4-20 mA signal.