4 Commissioning

P12

TB-13C FUNCTION SELECT

This selects the function of terminal TB-13C. Closing TB-13C to TB-2 (or opening in the case of setting
06) activates the selected function. The following functions can be selected:

01

NONE: Disables the TB-13C function.

02

0-10 VDC: Selects a 0-10 VDC signal (at TB-5) as the AUTO speed reference input.

03

4-20 mA: Selects a 4-20 mA signal (at TB-25) as the AUTO speed reference input.

04

PRESET SPEED #3: Selects PRESET SPEED #3 as the AUTO speed reference. The drive will operate
at the frequency programmed into Parameter 33.

05

INCREASE FREQUENCY: Increases the speed setpoint when using the MOP function. Refer to
Section 3.5.6.

06

EXTERNAL FAULT: Sets TB-13C as a normally closed external fault input. If TB-13C is open with
respect to TB-2, the drive will fault.

07

REMOTE KEYPAD: Selects the optional remote keypad as the control source. Refer to Parameter
14 - CONTROL.

08

DB FAULT: Sets TB-13C as a dynamic braking fault input when using the optional dynamic
braking module. When this input is activated by the dynamic braking module, the drive will
trip into a "dF" fault and the motor will coast to a stop. Refer to the manual included with the
Dynamic Braking option.

09

ACCEL/DECEL #2: Selects the acceleration and deceleration time programmed into Parameter
42 - ACCEL/DECEL #2.

P13

TB-15 OPEN COLLECTOR OUTPUT

This selects the status indication for the open-collector output at TB-15, and has the same selections
as Parameter 6 - TB-14 OPEN COLLECTOR OUTPUT.

P14 CONTROL

This selects the source of START/STOP and direction commands.

01

TERMINAL STRIP ONLY: The drive will only respond to START/STOP and direction commands
from the terminal strip.

02

REMOTE KEYPAD ONLY: The drive will only respond to START/STOP and direction commands
from the optional remote keypad.

03

TERMINAL STRIP OR REMOTE KEYPAD: Terminal TB-13A or TB-13C can be used to select terminal
strip control or remote keypad control. See Parameters 10 and 12.

NOTE
The STOP button on the optional remote keypad is always active as long as the serial
link remains intact.