Commissioning 4, 3 parameter menu – Lenze SCF frequency inverter User Manual

Page 33

Advertising
background image

Lenze 13466146 EDBSF01 v24 EN

33

Commissioning 4

4.3

Parameter Menu

NOTE: If the drive is equipped with the PI option, please refer to Appendix B for additional parameter
information.

NO.

PARAMETER NAME

RANGE OF ADJUSTMENT

FACTORY

DEFAULT
(NOTE 1)

01

LINE VOLTAGE

HIGH (01), LOW (02)

HIGH (01)

02

CARRIER FREQUENCY

4kHz (01), 6 kHz (02), 8 kHz (03), 10 kHz (04)

6 kHz (02)

03

START METHOD

NORMAL (01), START ON POWER UP (02),

START WITH DC BRAKE (03),

AUTO RESTART WITH DC BRAKE (04),

FLYING RESTART 1 (05),
FLYING RESTART 2 (06),

FLYING RESTART 3 (07)

NORMAL (01)

04

STOP METHOD

COAST (01), COAST WITH DC BRAKE (02),

RAMP (03), RAMP WITH DC BRAKE (04)

COAST (01)

05

STANDARD

SPEED SOURCE

KEYPAD (01), PRESET #1 (02),

0-10 VDC (03), 4-20 mA (04)

KEYPAD (01)

06
13

TB-14 OUTPUT
TB-15 OUTPUT

NONE (01), RUN (02), FAULT (03),

INVERSE FAULT (04), FAULT LOCKOUT (05),
AT SET SPEED (06), ABOVE PRESET #3 (07),

CURRENT LIMIT (08), AUTO SPEED (09),

REVERSE (10)

NONE (01)

08

TB-30 OUTPUT

NONE (01), 0-10 VDC FREQ (02),

2-10 VDC FREQ (03), 0-10 VDC LOAD (04),

2-10 VDC LOAD (05)

NONE (01)

09

TB-31 OUTPUT

NONE (01), 0-10 VDC LOAD (02)

2-10 VDC LOAD (03), DYNAMIC BRAKING (04)

NONE (01)

10

TB-13A FUNCTION

SELECT

NONE (01), 0-10 VDC (02), 4-20 mA (03),

PRESET SPEED #1 (04),RUN REVERSE (05),

START REVERSE (06), EXTERNAL FAULT (07),

REMOTE KEYPAD (08), DB FAULT (09),

AUXILIARY STOP (10), ACCEL/DECEL #2 (11)

NONE (01)

11

TB-13B FUNCTION

SELECT

NONE (01), 0-10 VDC (02), 4-20 mA (03),

PRESET SPEED #2 (04), DECREASE FREQ (05),

JOG FORWARD (06), JOG REVERSE (07)

AUXILARY STOP (08)

NONE (01)

NOTE 1: Factory defaults are shown for a 60 Hz base frequency. Refer to Parameter 48 for 50 Hz base frequency.