Installation 3

3.2.3 Input Wire Size Requirements

Input Wire Size Requirements

120 Vac 1 phase

208/240 Vac 1 phase

208/240 Vac 3 phase

400/480 Vac 3 phase

Model

AWG mm

2

Model

AWG mm

2

Model AWG mm

2

Model AWG mm

2

SM004S

14

2.5

S_204S

14

2.5

SM005S

14

2.5

S_205S

14

2.5

SM205

14

2.5

SM405

14

2.5

S_208S

14

2.5

SM010S

12

4.0

S_210S

14

2.5

SM210

14

2.5

SM410

14

2.5

SM015S

10

6.0

S_215S

14

2.5

SM215

14

2.5

SM415

14

2.5

S_220S

12

4.0

SM220

14

2.5

SM420

14

2.5

S_230S

10

6.0

SM230

14

2.5

SM430

14

2.5

SM250

12

4.0

SM450

14

2.5

SM275

8

10

SM475

12

4.0

SM2100

8

10

SM4100

10

6.0

SM2150

6

16

SM4150

8

10

3.2.4 Installation According to EMC Requirements

The SCM and SCL Series can be installed to meet the European standards for Electromagnetic
Compatibility (EMC) requirements. These requirements govern the permissible electromagnetic
emissions and immunity, both radiated and conducted, of a drive system.

The EMC requirements apply to the final installation in its entirety, not to the individual components
used. Because every installation is different, the recommended installation should follow these
guidelines as a minimum. Additional equipment (such as ferrite core absorbers on power conductors)
or alternative wiring practices may be required to meet conformance in some installations.

Filter: The input to the drive (or group of drives) must include a filter to reduce the electrical noise
reflected back to the AC Line. The SCL Series includes a filter that has been tested to meet the industrial
standards set by the EU, EN 61800-3 for conducted emissions and EN 55011 for radiated emissions
to class A compliance when installed in a control cabinet with a motor cable < 10m. The SCM can be
installed to meet these same standards when used with an appropriately installed external line filter.

EMC
Compliance with EN 61800-3/A11

Installation: Shielded cable must be used for all control and power cables
and exposed wiring must be kept as short as possible.

A

Screen clamps

B

Control cable

C

Low-capacitance motor cable

(core/core < 75 pF/m, core/screen < 150 pF/m)

D

Electrically conductive mounting plate

E

Filter

SM01-1

B

C

D

A

E