3 Installation

3.6.4 Preset Speeds & Speed Pot (2-Wire Start/Stop Control)

Maintained

RUN/STOP

Contact

1

2

25

13A

13E

13B

RUN

5

6

11

16

17

SIGNAL COMMON

0-10V DC INPUT

TB-13A FUNCTION SELECT

TB-13B FUNCTION SELECT

TB-13E FUNCTION SELECT

FORM A RELAY

SPEED POT POWER SUPPLY

DIGITAL INPUT REFERENCE

(PRESET SPEED #1

)

(PRESET SPEED #2

)

(PRESET SPEED #3

)

SPEED

POT

Speed Potentiometer

NOTE:

For preset speed control, all or some of the TB-13 terminals must be programmed
as preset speed selects. If only two or three preset speeds are required, only
two of the TB-13 terminals must be used. Refer to Section 4.4 Description of
Parameters (Parameters 31-37).

Program the PRESET SPEEDS (Parameters 31-37) to the desired values.

If speed pot control is desired when none of the preset speeds are selected
(all preset speed selects are open to TB-11), set STANDARD SPEED SOURCE
(Parameter 05) to 0-10 VDC (03).