Installation 3, 4 scl/scm power wiring diagram – Lenze SL User Manual

Page 17

Advertising
background image

Lenze 13466147 EDBSM01 v19 EN

17

Installation 3

3.4

SCL/SCM Power Wiring Diagram

4.5 lb-in / 0.5 Nm

0.24 in / 6 mm

10 lb-in / 1.2 Nm

0.35 in / 9 mm

18 lb-in / 2.0 Nm

0.5 in / 13 mm

15 HP

(11 kW)

7.5 - 10 HP

(5.5 - 7.5 kW)

0.25 - 5 HP

(0.37 - 4 kW)

L1

L1

L1

Input

Single Phase Models

Input

Three Phase Models

208/240V up to 5Hp

400/480V up to 7.5Hp

Input

Three Phase Models

208/240V 7.5Hp and larger

400/480V 10Hp and larger

Output

Output

L2/N

PE

B- B+

Input AC Voltage

Input AC Voltage

Input AC Voltage

PE lug on heatsink

PE lug on heatsink

L2 L3 B- B+

L2 L3

U

V

W PE PE

PES

PES

PES

3-Phase

AC Motor

3-Phase

AC Motor

T1 T2 T3 B- B+

+

-

DC

Bus

Voltage

Torque Requirements

WARNING!
•

DO NOT connect incoming AC power to output terminals U, V, W, or terminals B+,
B-! Severe damage to the drive will result.

•

Leakage current may exceed 3.5 mA AC. Minimum size of the protective earth
(PE) conductor shall comply with local safety regulations for high leakage current
equipment.

NOTE
•

WIRE AND GROUND IN ACCORDANCE WITH NEC OR CEC, AND ALL APPLICABLE
LOCAL CODES.

•

Motor wires MUST be run in a separate steel conduit away from control wiring and
incoming AC power wiring.

•

Do not install contactors between the drive and the motor without consulting Lenze
Americas for more information. Failure to do so may result in drive damage.

•

Use only UL and CSA listed and approved wire.

•

Minimum wire voltage rating is 300 V for 120, 208, and 240 Vac systems, and 600
V for 400 and 480 Vac systems.

•

Wire gauge must be based on a minimum of 125% of the rated input/output current
of the drive, and a minimum 75°C insulation rating. Use copper wire only.