Installation 3, 4 scl/scm power wiring diagram – Lenze SL User Manual

Page 17

Advertising
background image

Lenze 13466147 EDBSM01 v19 EN

17

Installation 3

3.4

SCL/SCM Power Wiring Diagram

4.5 lb-in / 0.5 Nm

0.24 in / 6 mm

10 lb-in / 1.2 Nm

0.35 in / 9 mm

18 lb-in / 2.0 Nm

0.5 in / 13 mm

15 HP

(11 kW)

7.5 - 10 HP

(5.5 - 7.5 kW)

0.25 - 5 HP

(0.37 - 4 kW)

L1

L1

L1

Input

Single Phase Models

Input

Three Phase Models

208/240V up to 5Hp

400/480V up to 7.5Hp

Input

Three Phase Models

208/240V 7.5Hp and larger

400/480V 10Hp and larger

Output

Output

L2/N

PE

B- B+

Input AC Voltage

Input AC Voltage

Input AC Voltage

PE lug on heatsink

PE lug on heatsink

L2 L3 B- B+

L2 L3

U

V

W PE PE

PES

PES

PES

3-Phase

AC Motor

3-Phase

AC Motor

T1 T2 T3 B- B+

+

-

DC

Bus

Voltage

Torque Requirements

WARNING!

DO NOT connect incoming AC power to output terminals U, V, W, or terminals B+,
B-! Severe damage to the drive will result.

Leakage current may exceed 3.5 mA AC. Minimum size of the protective earth
(PE) conductor shall comply with local safety regulations for high leakage current
equipment.

NOTE

WIRE AND GROUND IN ACCORDANCE WITH NEC OR CEC, AND ALL APPLICABLE
LOCAL CODES.

Motor wires MUST be run in a separate steel conduit away from control wiring and
incoming AC power wiring.

Do not install contactors between the drive and the motor without consulting Lenze
Americas for more information. Failure to do so may result in drive damage.

Use only UL and CSA listed and approved wire.

Minimum wire voltage rating is 300 V for 120, 208, and 240 Vac systems, and 600
V for 400 and 480 Vac systems.

Wire gauge must be based on a minimum of 125% of the rated input/output current
of the drive, and a minimum 75°C insulation rating. Use copper wire only.