4 commissioning – Lenze SL User Manual

Page 38

Advertising
background image

38

Lenze 13466147 EDBSM01 v19 EN

4 Commissioning

07

JOG FORWARD: Close TB-13B to TB-11 to JOG in the forward direction. The drive will run at
PRESET SPEED #2 (Parameter 32) when in JOG mode.

08

JOG REVERSE: Close TB-13B to TB-11 to JOG in the reverse direction. The drive will run at PRESET
SPEED #2 (Parameter 32) when in JOG mode.

WARNING!

When operating in JOG mode, the STOP signal and the AUXILIARY STOP function
(see Parameters 10-12) WILL NOT stop the drive. To stop the drive, remove the JOG
command.

JOG REVERSE will operate the drive in reverse rotation even if ROTATION DIRECTION
(Parameter 17) is set to FORWARD ONLY.

09

EXTERNAL FAULT: Sets TB-13B as a normally closed external fault input. Open TB-13B to TB-11
to trip the drive.

10

INVERSE EXTERNAL FAULT: Sets TB-13B as a normally open external fault input. Close TB-13B
to TB-11 to trip the drive.

11

AUXILIARY STOP: When TB-13B is opened with respect to TB-11, the drive will decelerate to a
STOP (even if STOP METHOD is set to COAST) at the rate set into ACCEL/DECEL #2 (Parameter
42).

12

ACCEL/DECEL #2: Selects the acceleration and deceleration time programmed into Parameter
42 - ACCEL/DECEL #2.

13

REMOTE KEYPAD: When the Remote Keypad option is being used, TB-13B must be set to this
function. Also, TB-13E (Parameter 12) must be set for REMOTE KEYPAD (21), and CONTROL
(Parameter 14) must be set to REMOTE KEYPAD ONLY (02).

NOTE
If the drive is commanded to JOG while running, the drive will enter JOG mode and run at
PRESET SPEED #2 (Parameter 32). When the JOG command is removed, the drive will STOP.

P12

TB-13E FUNCTION SELECT

Parameter P12 selects the function of terminal TB-13E. This terminal can be configured as a digital
input (settings 01 to 10) or a digital status output (settings 11 to 20). When used as an input, closing
TB-13E to TB-11 (or opening in the case of settings 07 and 09) activates the selected function.

When used as an output, P12 can provide the drive's status for monitoring. If the Remote Keypad
option is being used, this parameter must be set to REMOTE KEYPAD (21).

The following input functions can be selected for P12:

01

NONE: Disables the TB-13E function.

02

0-10 VDC: Selects a 0-10 VDC signal (at TB-5) as the AUTO speed reference input.

03

4-20 mA: Selects a 4-20 mA signal (at TB-25) as the AUTO speed reference input.

04

PRESET SPEED #3: Selects PRESET SPEED #3 as the speed reference. The drive will operate at
the frequency programmed into Parameter 33.