3 Installation

3.6.2 Two-Wire Start/Stop Control

Maintained

RUN/STOP

Contact

(FORWARD)

1

2

25

13A

13E

13B

RUN

5

6

11

16

17

SIGNAL COMMON

0-10V DC INPUT

TB-13A FUNCTION SELECT

TB-13B FUNCTION SELECT

TB-13E FUNCTION SELECT

4-20mA INPUT

FORM A RELAY

-

+

+

SPEED POT POWER SUPPLY

DIGITAL INPUT REFERENCE

Maintained

RUN/STOP

Contact

(REVERSE)

RUN REVERSE

2-Wire Start/Stop Control

NOTE

Close TB-1 to TB-11 to RUN, and open to STOP. TB-1 functions as a RUN input for
two-wire start/stop circuits, and a STOP input for three-wire start/stop circuits.
Refer to Section 3.6.3

If reverse direction is required, set ROTATION (Parameter 17) to FORWARD AND
REVERSE (02), and program TB-13A (Parameter 10) to RUN REVERSE (06). Close
TB-13A to TB-11 to RUN in the reverse direction, and open to STOP.

For 0-10 VDC or 4-20 mA speed control, set STANDARD SPEED SOURCE
(Parameter 05) to 0-10 VDC (03) or 4-20 mA (04).