3 installation – Lenze SL User Manual
Page 22
![background image](/manuals/566088/22/background.png)
22
Lenze 13466147 EDBSM01 v19 EN
3 Installation
3.6.2 Two-Wire Start/Stop Control
Maintained
RUN/STOP
Contact
(FORWARD)
1
2
25
13A
13E
13B
RUN
5
6
11
16
17
SIGNAL COMMON
0-10V DC INPUT
TB-13A FUNCTION SELECT
TB-13B FUNCTION SELECT
TB-13E FUNCTION SELECT
4-20mA INPUT
FORM A RELAY
-
+
+
SPEED POT POWER SUPPLY
DIGITAL INPUT REFERENCE
Maintained
RUN/STOP
Contact
(REVERSE)
RUN REVERSE
2-Wire Start/Stop Control
NOTE
•
Close TB-1 to TB-11 to RUN, and open to STOP. TB-1 functions as a RUN input for
two-wire start/stop circuits, and a STOP input for three-wire start/stop circuits.
Refer to Section 3.6.3
•
If reverse direction is required, set ROTATION (Parameter 17) to FORWARD AND
REVERSE (02), and program TB-13A (Parameter 10) to RUN REVERSE (06). Close
TB-13A to TB-11 to RUN in the reverse direction, and open to STOP.
•
For 0-10 VDC or 4-20 mA speed control, set STANDARD SPEED SOURCE
(Parameter 05) to 0-10 VDC (03) or 4-20 mA (04).