Commissioning 4

P10

TB-13A FUNCTION SELECT

P10 selects the function of terminal TB-13A. Closing TB-13A to TB-11 (or opening in the case of settings
08 and 10) activates the selected function. The following functions can be selected:

01

NONE: Disables the TB-13A function.

02

0-10 VDC: Selects a 0-10 VDC signal (at TB-5) as the AUTO speed reference input.

03

4-20 mA: Selects a 4-20 mA signal (at TB-25) as the AUTO speed reference input.

04

PRESET SPEED #1: Selects PRESET SPEED #1 as the speed reference. The drive will operate at
the frequency programmed into Parameter 31.

05

START FORWARD: Sets up the drive for a 3-wire start/stop circuit. Momentarily close TB-13A
to TB-11 to start the drive, and momentarily open TB-1 to TB-11 to stop.

06

RUN REVERSE: Close TB-13A to TB-11 to run in the reverse direction, and open to stop. Close
TB-1 to TB-11 to run in the forward direction and open to stop.

07

START REVERSE: Momentarily close TB-13A to TB-11 to start the drive in the reverse direction,
and momentarily open TB-1 to TB-11 to stop. Parameter 17 - ROTATION must be set to FORWARD
AND REVERSE (02), and TB-13E must be used for START FORWARD.

08

EXTERNAL FAULT: Sets TB-13A as a normally closed external fault input. Open TB-13A to TB-11
to trip the drive.

09

INVERSE EXTERNAL FAULT: Sets TB-13A as a normally open external fault input. Close TB-13A
to TB-11 to trip the drive.

10

AUXILIARY STOP: When TB-13A is opened with respect to TB-11, the drive will decelerate to a
STOP (even if STOP METHOD is set to COAST) at the rate set into ACCEL/DECEL #2 (Parameter
42).

11

ACCEL/DECEL #2: Selects the acceleration and deceleration time programmed into ACCEL/
DECEL #2 (Parameter 42).

P11

TB-13B FUNCTION SELECT

P11 selects the function of terminal TB-13B. Closing TB-13B to TB-11 (or opening in the case of settings
09 and 11) activates the selected function. The following functions can be selected:

01

NONE: Disables the TB-13B function.

02

0-10 VDC: Selects a 0-10 VDC signal (at TB-5) as the AUTO speed reference input.

03

4-20 mA: Selects a 4-20 mA signal (at TB-25) as the AUTO speed reference input.

04

PRESET SPEED #2: Selects PRESET SPEED #2 as the speed reference. The drive will operate at
the frequency programmed into Parameter 32.

05

DECREASE FREQ: Closing TB-13B to TB-11 will decrease the speed setpoint until the contact is
opened. TB-13E must be programmed for INCREASE FREQ.

06

START FORWARD: Sets up the drive for a 3-wire start/stop circuit. Momentarily close TB-13B to
TB-11 to start the drive, and momentarily open TB-1 to TB-11 to stop.