4 commissioning – Lenze SL User Manual

Page 36

Advertising
background image

36

Lenze 13466147 EDBSM01 v19 EN

4 Commissioning

P05

STANDARD SPEED SOURCE

P05 selects the speed reference source when the drive is in STANDARD speed mode. The following
speed references can be selected:

01

KEYPAD: Use the p and q buttons to scroll to the desired speed.

02

PRESET SPEED #1: Drive will operate at the frequency set in Parameter 31.

03

0-10 VDC: Drive will respond to a 0-10 VDC signal wired to TB-5 (+) and TB-2 (-).

04

4-20 mA: Drive will respond to a 4-20 mA signal wired to TB-25 (+) and TB-2 (-).

P06

RELAY OUTPUT

P06 selects the status indication for the normally open relay output at TB-16 and TB-17:

01

NONE: Disables the relay output.

02

RUN: Closes upon a START command. Opens if the drive is in a STOP state, the drive faults, or
input power is removed. DC braking is considered a STOP state.

03

FAULT: Closes if there is no fault condition. Opens if the drive faults, or input power is removed.

04

INVERSE FAULT: Closes if the drive faults. Opens if there is no fault condition.

05

FAULT LOCKOUT: Closes when input power is applied. Opens if three restart attempts are
unsuccessful, or if input power is removed.

06

AT SET SPEED: Closes if the drive is within + 0.5 Hz of the speed setpoint.

07

ABOVE PRESET SPEED #3: Closes if the output frequency exceeds PRESET SPEED #3 (Parameter
33). Opens if the output frequency is equal to or less than PRESET SPEED #3.

08

CURRENT LIMIT: Closes if the output current exceeds the CURRENT LIMIT setting. Opens if the
output current is equal to or less than CURRENT LIMIT (see Parameter 25).

09

AUTOMATIC SPEED MODE: Closes if an AUTOMATIC (terminal strip) speed reference is active.
Opens if a STANDARD (Parameter 5) speed reference is active.

10

REVERSE: Closes when reverse rotation is active. Opens when forward rotation is active (see
Parameter 17 - ROTATION DIRECTION).