Commissioning 4 – Lenze SL User Manual

Page 31

Advertising
background image

Lenze 13466147 EDBSM01 v19 EN

31

Commissioning 4

4.3

Parameter Menu

No.

Parameter Name

Range of Adjustment

Factory

Default

01

LINE VOLTAGE

HIGH (01)

LOW (02)

HIGH (01)

02

CARRIER FREQUENCY

4kHz (01)

6 kHz (02)
8 kHz (03)

10 kHz (04)

6 kHz (02)

03

START METHOD

NORMAL (01)

START ON POWER UP (02)

START WITH DC BRAKE (03)

AUTO RESTART WITH DC BRAKE (04)

FLYING RESTART 1 (05)
FLYING RESTART 2 (06)
FLYING RESTART 3 (07)

NORMAL (01)

04

STOP METHOD

COAST (01)

COAST WITH DC BRAKE (02)

RAMP (03)

RAMP WITH DC BRAKE (04)

COAST (01)

05

STANDARD SPEED

SOURCE

KEYPAD (01),

PRESET #1 (02),

0-10 VDC (03),

4-20 mA (04)

KEYPAD (01)

06

RELAY OUTPUT

NONE (01), RUN (02), FAULT (03),

INVERSE FAULT (04), FAULT LOCKOUT (05),
AT SET SPEED (06), ABOVE PRESET #3 (07),

CURRENT LIMIT (08), AUTO SPEED (09),

REVERSE (10)

NONE (01)

10

TB-13A FUNCTION

SELECT

NONE (01), 0-10 VDC (02), 4-20 mA (03),

PRESET SPEED #1 (04),

START FORWARD (05),RUN REVERSE (06),

START REVERSE (07),

EXTERNAL FAULT (08),

INVERSE EXT FAULT (09),

AUXILIARY STOP (10),

ACCEL/DECEL #2 (11)

NONE (01)

11

TB-13B FUNCTION

SELECT

NONE (01), 0-10 VDC (02), 4-20 mA (03),

PRESET SPEED #2 (04), DECREASE FREQ (05),

START FORWARD (06), JOG FORWARD (07),

JOG REVERSE (08), EXTERNAL FAULT (09),

INVERSE EXT FAULT (10), AUX. STOP (11),

ACCEL/DECEL #2 (12), REMOTE KEYPAD (13)

NONE (01)

Advertising