Electrical installation

Power terminals

5

l

105

EDKCSDX064 DE/EN/FR 3.0

Cable cross−sections and screw−tightening torques

Cable type Wire end ferrule

Possible cable
cross−sections

Tightening torque

Stripping length

Plug connectors X23 and X24

Rigid

˘

0.2 ... 10 mm

2

(AWG 24 ... 8)

1.2 ... 1.5 Nm

(10.6 ... 13.3 lb−in)

5 mm for screw
connections

10 mm for spring
connections

Flexible

Without wire end
ferrule

0.2 ... 10 mm

2

(AWG 24 ... 8)

Insulated with wire
end ferrule

0.25 ... 6 mm

2

(AWG 22 ... 10)

Insulated with wire
end ferrule

0.25 ... 4 mm

2

(AWG 22 ... 12)

Plug connector X25

Flexible

Insulated with wire
end ferrule

0.25 ... 2.5 mm

2

(AWG 22 ... 12)

0.5 ... 0.8 Nm

(4.4 ... 7.1 lb−in)

5 mm for screw
connections

10 mm for spring
connections

Without wire end
ferrule

0.2 ... 2.5 mm

2

(AWG 24 ... 12)

Shielded cables
The following factors decisively determine the effect of the shielded cables:

ƒ

Good shield connection

Ensure a contact surface as large as possible

ƒ

Low shield resistance

Only use shields with tin−plated or nickel−plated copper braids (shields
with steel braids cannot be used).

ƒ

High overlap rate of the braid

At least 70 ... 80 % with 90° overlap angle

The ECSZS000X0B shield mounting kit includes a wire clamp and shield sheet.