Electrical installation

Power terminals
Connection to the DC bus (+U

G

, −U

G

)

5

l

108

EDKCSDX064 DE/EN/FR 3.0

Cable cross−section

Cable
length
(module/
module)

Wire end ferrule

Cable
cross−section

Tightening torque

Stripping length

Up to 20 m

Without wire end
ferrule

6 mm

2

(AWG 10)

1.2 ... 1.5 Nm

(10.6 ... 13.3 lb−in)

5 mm for screw
connection

10 mm for spring
connection

With insulated wire
end ferrule

> 20 m

Without wire end
ferrule

10 mm

2

(AWG 8)

With insulated wire
end ferrule
Use pin−end
connectors for
wiring!

Fuses

ƒ

Mains fuses are not included in the Lenze delivery program. Use standard
fuses.

ƒ

When using ECSxE power supply modules which are fused on the supply
side the DC−bus supply need not be fused.

ƒ

When ECS axis modules are supplied by devices of the 82xx and 93xx
series with a continuous DC current > 40 A, install the following fuses
between the supplying device and the ECS devices:

Fuse

Support

Value [A]

Lenze type

Lenze type

50

EFSGR0500ANIN

EFH20007

ƒ

Observe the national and regional regulations (VDE, UL, EVU, ...).

J

Warnings!

ƒ

Use UL−approved cables, fuses and fuse holders only.

ƒ

UL fuse:
– Voltage 500 ... 600 V
– Tripping characteristic "H", "K5" or "CC"