Electrical installation

Wiring of system bus (CAN)

5

l

129

EDKCSDX064 DE/EN/FR 3.0

Bus cable length

)

Note!

The permissible cable lengths must be observed.

1. Check the compliance with the total cable length in Tab. 5−1.
The baud rate determines the total cable length.

CAN baud rate [kbit/s]

Max. bus length [m]

50

1500

125

630

250

290

500

120

1000

25

Tab. 5−1

Total cable length

2. Check the compliance with the segment cable length in Tab. 5−2.
The segment cable length is determined by the cable cross−section used and the
number of nodes. Without a repeater, the segment cable length corresponds to
the total cable length.

Number of nodes

Cable cross−section

0.25 mm

2

0.5 mm

2

0.75 mm

2

1.0 mm

2

2

240 m

430 m

650 m

940 m

5

230 m

420 m

640 m

920 m

10

230 m

410 m

620 m

900 m

20

210 m

390 m

580 m

850 m

32

200 m

360 m

550 m

800 m

63

170 m

310 m

470 m

690 m

Tab. 5−2

Segment cable length

3. Compare the two values detected.
If the value detected from Tab. 5−2 is smaller than the total cable length to be
provided from Tab. 5−1 , repeaters must be used. Repeaters divide the total cable
length into segments.

,

Operating instructions for ECS axis module

Here you can find detailed information on how to use repeaters.