Sicherheitshinweise

Sicherheitshinweise für die Installation nach UL

2

l

22

EDKCSDX064 DE/EN/FR 3.0

2.4

Sicherheitshinweise für die Installation nach UL

J

Warnings!

General markings:

ƒ

Use 60/75 °C or 75 °C copper wire only.

ƒ

Maximum ambient temperature 55 °C, with reduced output
current.

Markings provided for the supply units:

ƒ

Suitable for use on a circuit capable of delivering not more than
5000 rms symmetrical amperes, 480 V max, when protected by
K5 or H Fuses (400/480 V devices).

ƒ

Alternate − Circuit breakers (either inverse−time, instantaneous
trip types or combination motor controller type E) may be used in
lieu of above fuses when it is shown that the let−through
energy (i

2

t) and peak let−through current (I

p

) of the inverse−time

current−limiting circuit breaker will be less than that of the
non−semiconductor type K5 fuses with which the drive has been
tested.

ƒ

Alternate − An inverse−time circuit breaker may be used, sized
upon the input rating of the drive, multiplied by 300 %.

Markings provided for the inverter units:

ƒ

The inverter units shall be used with supply units which are
provided with overvoltage devices or systems in accordance with
UL840 2nd ed., Table 5.1.

ƒ

The devices are provided with integral overload and integral
thermal protection for the motor.

ƒ

The devices are not provided with overspeed protection.

Terminal tightening torque of lb−in (Nm)

Terminal

lb−in

Nm

X21, X22, X23, X24

10.6 ... 13.3

1.2 ... 1.5

X4, X6, X14

1.95 ... 2.2

0.22 ... 0.25

X25

4.4 ... 7.1

0.5 ... 0.8

Wiring diagram AWG

Terminal

AWG

X21, X22, X23, X24

12 ... 8

X4, X6, X14

28 ... 16

X25

24 ... 12