background image

Mechanical installation

Important notes

4

17

EDBCSXKXXX EN 1.0

4

Mechanical installation

4.1

Important notes

ƒ ECSxKxxx capacitor modules are provided with IP20 protection and can therefore

only be used for installation into control cabinets.
– For thermally separated mounting (ECSDKxxx): IP54 on the heatsink side

ƒ If the cooling air contains air pollutants (dust, fluff, grease, aggressive gases):

– Take suitable preventive measures , e.g. separate air duct, installation of filters,

regular cleaning.

ƒ Ensure free space!

– Ensure unimpeded ventilation of cooling air and outlet of exhaust air.
– You can install several capacitor modules next to each other without any clearance

in a control cabinet.

– Allow a free space of 50 mm above and below other installations or limitations.

ƒ The mounting plate of the control cabinet must be electrically conductive.
ƒ In case of continuous vibrations or shocks use shock absorbers.

Possible mounting positions
Vertically on the mounting plate with DC-bus connections at the top

Mounting techniques
ƒ With fixing rails (standard,  18)
ƒ Thermal separation (”push-through technique”,  19)
ƒ In ”cold plate” technique ( 21)