4 power connections, 1 terminal assignment of the power connections, 2 fusing the dc-bus supply – Lenze ECSxK series User Manual

Page 28: 3 specification of the cables used, Terminal assignment of the power connections, Fusing the dc-bus supply, Specification of the cables used, Electrical installation, Warnings

Advertising
background image

Electrical installation

Power connections

Terminal assignment of the power connections

5

28

EDBCSXKXXX EN 1.0

5.4

Power connections

5.4.1

Terminal assignment of the power connections

Terminal

Function

Electrical data

X23

Connection of DC-bus voltage

X23/+UG

Positive supply of DC bus voltage

X23/+UG

Positive supply of DC-bus voltage

D

d t

li ti

d t

X23/-UG

Negative supply of DC bus voltage

Dependent on application and type

0 770 V

X23/-UG

Negative supply of DC-bus voltage

0 ... 770 V

X23/PE

Earth connection

X23/PE

Earth connection

5.4.2

Fusing the DC-bus supply

When ECSxE power supply modules with a mains-side protection are used, the DC-bus

cables do not need to be fused.
When using capacitor modules in the DC-bus connection with basic devices of the 82xx

and 93xx series, use the following fuses:

Fuse

Support

Value [A]

Lenze type

Lenze type

50

EFSGR0500ANIN

EFH20007

Warnings!

ƒ

Use UL-approved cables, fuses and fuse holders only.

ƒ

UL fuse:

Voltage 500 ... 600 V

Tripping characteristic ”H”, ”K5” or ”CC”

5.4.3

Specification of the cables used

The cables used must comply with the required approvals at the place of installation

(e. g. UL).
Installation of the cables to EN 60204-1 (1998)

Shielded cables
Observe the following to increase the effect of shielded cables:
ƒ A good shield connection:

– Ensure a contact surface as large as possible

ƒ Low shield resistance:

– Only use shields with tin-plated or nickel-plated copper braids (shields with steel

braids cannot be used).

ƒ High contact ratio of the shield braid:

– At least 70 ... 80 % with 90 ° overlap angle