Electrical installation

Wiring

Operation with ECSxE power supply module

5

31

EDBCSXKXXX EN 1.0

5.6

Wiring

5.6.1

Operation with ECSxE power supply module

Install the capacitor module ECSxKxxx between the power supply module and the axis

module(s).
If the total cable length in the DC-bus connection is longer than 5 m, install the capacitor

module as close as possible to the axis module with the highest power.

Stop!

ƒ

Permanently bridge the charging current limitation (X26) of the capacitor

module (X26 = HIGH).

ƒ

Only release the controller (X6/SI1 = HIGH) if the power supply module

ECSxE displays ”Ready for operation” (X6/DO1 = HIGH).

L3

N

PE

L1

L2

F1...F3

Z1

F4

K1

ECSxKxxx

K1

K1

L1

L2

L3

ECSxExxx

PE

X21

+UG

+UG

+UG

+UG

+UG

-UG

-UG

-UG

-UG

-UG

PE

PE

PE

PE

PE

X22

X23

Off

On

+UG

BR1

X26

BR0

PES

PES

U

V W

ECSxAxxx

X23

PE

X24

B1 B2

X25

X7

M

3~

PE

PES

PES

R

J

*1

2

6

. . .

T1

T2

X6

DI1

DI2

DO1

D24

+24V

GND

GND

24 V DC

+

-

Ctrl. enable

K1

ECSXX004

Fig.5-2

Wiring of the capacitor module ECSxK with power supply module ECSxE

HF shield termination by large-surface PE connection
Twisted cables

* 1

System cable - feedback

Ctrl.

enable Terminal X6/SI1 of the connected axis modules (controller enable)

Show/Hide Bookmarks