Electrical installation

Important notes

Protection of persons

5

23

EDBCSXKXXX EN 1.0

5

Electrical installation

5.1

Important notes

Stop!

The capacitor module contains electrostatically sensitive components.
Prior to assembly and service operations, the personnel must be free of

electrostatic charge.

5.1.1

Protection of persons

Danger!

ƒ

Before working on the capacitor module, check that no voltage is applied to

the power terminals,

because the power terminals +UG and -UG remain live for at least three

minutes after mains switch-off.

because the power terminals +UG and -UG remain live when the motor is

stopped.

ƒ

If an error occurs (short circuit to frame or earth fault), a DC residual current

may occur in the PE conductor. If an earth-leakage circuit breaker (residual

current device) is used to protect against direct or indirect contact, only the

use of an earth-leakage circuit breaker of type B is permissible on the

current supply side. If not, another protective measure is to be used, as for

example, separation from the environment by double or reinforced

insulation or separation from the mains by using a transformer.