Electrical installation

Important notes

Device protection

5

24

EDBCSXKXXX EN 1.0

5.1.2

Device protection

Stop!

ƒ

All pluggable connection terminals must only be connected or disconnected

when no voltage is applied.

ƒ

The power terminals +UG, -UG and PE are not protected against polarity

reversal.

When wiring, observe the polarity of the power terminals!

ƒ

The power may only be converted if the power supply module in the power

system is ready for operation and the charging current limitation is bridged.

Otherwise the charging current limitation can be destroyed.

ƒ

If the charging current limitation is active, a cyclic switching of the mains

voltage at the power supply module can overload and destroy the capacitor.

Therefore, at least three minutes have to pass between two starting

operations in case of cyclic mains switching over a longer period of time!

5.1.3

Electrical isolation

Bridging of the charging current

limitation

DC bus

Double insulation

X26

X23/+UG, -UG

Fig.5-1

Electrical isolation