Commissioning, 4 drive monitoring, 5 controlling the drive – Lenze E94P PositionServo Modbus User Manual

Page 22: 6 changing drive parameters

Advertising
background image

22

P94MOD01C

Commissioning

4.4 Drive Monitoring

The master/client can read the drive parameters as long as Modbus communications are enabled.

NOTE:
The complete list of variables can be found in the PositionServo Programming Manual (PM94P01, PM94M01).

4.5 Controlling the Drive

Controlling the drive over Modbus is essentially identical to controlling the drive from the User’s program. The
list of variables and their functionality is identical for both User’s program and Modbus control. Refer to the
variable list in the PositionServo Programming Manual for the functionality of the drive’s variables.

4.6 Changing Drive Parameters

To change drive parameters, simply write to the appropriate register as listed in the PositionServo Programming
Manual (PM94P01 or PM94M01).

4.7 EIA-485 (RS485) Parameters

Drive variables #172-176 are EIA-485 (RS485) communication programming parameters specifically for
configuration of the EIA-485 interface.

Table 5: EIA-485 (RS485) Variables - Excerpted from PS Variable List

PID

Variable Name

Type Format EPM Access Description

Units

172

VAR_SERIAL_ADDRESS

W

Y

R/W RS485 drive ID. Range: 0 - 254

173

VAR_MODBUS_BAUDRATE

W

Y

R/W

Baud rate for Modbus operations:
2 - 9600
3 - 19200
4 - 38400

5 - 57600
6 - 115200

174

VAR_MODBUS_DELAY

W

Y

R/W

Modbus reply delay in mS
Range: 0 - 1000

mS

175

VAR_RS485_CONFIG

W

Y

R/W

RS485 configuration:
0 - normal IP over PPP
1 - ModBus

176

VAR_PPP_BAUDRATE

NOTE: Does NOT apply

to MVOB.

W

Y

R/W

RS232/485 (normal mode) baud rate:
2 - 9600
3 - 19200
4 - 38400

5 - 57600
6 - 115200