Reference, 6 reference – Lenze E94P PositionServo Modbus User Manual

Page 29

Advertising
background image

29

P94MOD01C

Reference

6 Reference

6.1 PID List with Modbus Values

This is a condensed PID List to show the corresponding Modbus 4X Registers for PIDs 1-256. Modbus RTU
can not access beyond PID256. For the complete variable list refer to the PositionServo Programming Manual
(PM94P01 or PM94M01).
These variables can be accessed from the user’s program or any supported communications interface protocol.
From the user program, any variable can be accessed by either its variable name or by its index value (using the
syntax: @<VARINDEX> , where <VARINDEX> is the variable index from the PID List. From the communications
interface any variable can be accessed by its index value.
The column “

Type” indicates the type of variable:

mtr

Motor: denotes a motor value

mtn

Motion: writing to an “mtn” variable could cause the start of motion

vel

Velocity: denotes a velocity or velocity scaling value

The column “

Format” provides the native format of the variable:

W

32 bit integer

F

float (real)

When setting a variable via an external device the value can be addressed as floating or integer. The value will
automatically adjusted to fit it’s given form.
The column “

EPM” shows if a variable has a non-volatile storage space in the EPM memory:

Y

Variable has non-volatile storage Space in EPM

N

Variable does not exist in EPM memory

The user’s program uses a RAM (volatile) ‘copy’ of the variables stored on the EPM. At power up all RAM copies
of the variables are initialized with the EPM values. The EPM’s values are not affected by changing the variables
in the user’s program. When the user’s program reads a variable it always reads from the RAM (volatile) copy
of the variable. Communications Interface functions can change both the volatile and non-volatile copy of the
variable. If the host interface requests a change to the EPM (non-volatile) value, this change is done both in the
user program’s RAM memory as well as in the EPM. Interface functions have the choice of reading from the
RAM (volatile) or from the EPM (non-volatile) copy of the variable.
The column “

Access” lists the user’s access rights to a variable:

R

read only

W

write only

R/W read/write
Writing to an R (read-only) variable or reading from a W (write-only) variable will not work.
The column “

Units” shows units of the variable. Units unique to this manual that are used for motion are:

UU

user units

EC

encoder counts

S seconds
PPS

pulses per sample. Sample time is 512

ms - servo loop rate

PPSS pulses per sample per sample. Sample time is 512

ms - servo loop rate

Advertising