NOTE:

In true Modbus, 3X and 4X Registers are numbered starting at 1. This is known as ‘one based’ addressing.
However, when transmitted to a slave over the serial link, the actual address transmitted is one less.
Some Modbus masters will allow for the first register number to be 0. This is known as ‘zero based’
addressing. If this is the case, the Modbus register numbers listed in this manual must be offset by -1 to
properly program a master using ‘zero-based’ addressing.

Index

Name

Type

Format

EPM

Access

Description

Range

Unit

RAM

Registers

32bit

Integer
Access

4X

Register #

RAM

Register

32bit
Float

Access

4X

Register #

EPM

Reg Copy

32bit

Integer
Access

4X

Register #

EPM

Reg Copy

32bit
Float

Access

4X

Register #

RAM

Register

16bit

Signed

Integer

4X

Register #

EPM

INT16

4X

Register #

1

VAR_IDSTRING

N

R

Drive’s identification string

3

515

1027

1539

2050

2306

2

VAR_NAME

Y

R/W

Drive’s symbolic name

5

517

1029

1541

2051

2307

3

VAR_SERIAL_NUMBER

R

Drive’s serial number

7

519

1031

1543

2052

2308

4

VAR_MEM_INDEX

R/W

Position in RAM file

(0 - 32767)

9

521

1033

1545

2053

2309

5

VAR_MEM_VALUE

R/W

Value to be read or written to the RAM file

11

523

1035

1547

2054

2310

6

VAR_MEM_INDEX_
INCREMENT

R/W

Holds value the MEM_INDEX will modify once
the R/W operation is complete

13

525

1037

1549

2055

2311

7

VAR_VELOCITY_ACTUAL

R

Actual measured motor velocity
NOTE: Only applicable to MVOB drives with
Firmware 4.00 and higher.

15

527

1039

1551

2056

2312

8

VAR_RSVD_2

17

529

1041

1553

2057

2313

9

VAR_DFAULT

R

Drive Default Settings

19

531

1043

1555

2058

2314

10

VAR_M_ID

mtr

Y

R/W*

Motor ID

21

533

1045

1557

2059

2315

11

VAR_M_MODEL

mtr

Y

R/W*

Motor model

23

535

1047

1559

2060

2316

12

VAR_M_VENDOR

mtr

Y

R/W*

Motor vendor

25

537

1049

1561

2061

2317

13

VAR_M_ESET

mtr

Y

R/W*

Motor Feedback Resolver: ‘Positive for CW’
0 - none
1 - Positive for CW

0 - 1

27

539

1051

1563

2062

2318

14

VAR_M_HALLCODE

mtr

Y

R/W*

Hallcode index

0 - 5

29

541

1053

1565

2063

2319

15

VAR_M_HOFFSET

mtr

Y

R/W*

Reserved

31

543

1055

1567

2064

2320

16

VAR_M_ZOFFSET

mtr

Y

R/W*

Resolver Offset

0 - 360

33

545

1057

1569

2065

2321

17

VAR_M_ICTRL

mtr

Y

R/W*

Reserved

35

547

1059

1571

2066

2322

18

VAR_M_JM

mtr

Y

R/W*

Motor moment of inertia Jm

0 - 0.1

Kgm2

37

549

1061

1573

2067

2323

19

VAR_M_KE

mtr

Y

R/W*

Motor voltage or back EMF constant Ke

1 - 500

V/Krpm

39

551

1063

1575

2068

2324

20

VAR_M_KT

mtr

Y

R/W*

Motor torque or force constant Kt

0.01 - 10

Nm/A

41

553

1065

1577

2069

2325

21

VAR_M_LS

mtr

Y

R/W*

Motor phase-to-phase inductance Lm

0.1 - 500

mH

43

555

1067

1579

2070

2326

22

VAR_M_RS

mtr

Y

R/W*

Motor phase-to-phase resistance Rm

0.01 - 500

[Ohm]

45

557

1069

1581

2071

2327

23

VAR_M_MAXCURRENT

mtr

Y

R/W*

Motor’s max current(RMS)

0.5 - 50

[A]mp

47

559

1071

1583

2072

2328

24

VAR_M_MAXVELOCITY

mtr

Y

R/W*

Motor’s max velocity

500 - 20000

RPM

49

561

1073

1585

2073

2329

25

VAR_M_NPOLES

mtr

Y

R/W*

Motor’s poles number

2 - 200

51

563

1075

1587

2074

2330

26

VAR_M_ENCODER

mtr

Y

R/W*

Encoder resolution

256 - 65536
* 12/Npoles

PPR

53

565

1077

1589

2075

2331

27

VAR_M_TERMVOLTAGE

mtr

Y

R/W*

Nominal Motor’s terminal voltage

50 - 800

[V]olt

55

567

1079

1591

2076

2332

28

VAR_M_FEEDBACK

mtr

Y

R/W*

Feedback type
1 - Encoder; 2 - Resolver

1 - 2

57

569

1081

1593

2077

2333

29

VAR_ENABLE_SWITCH_
TYPE

W

Y

R/W

Enable switch function
0 - inhibit only; 1 - Run

0 - 1

Bit

59

571

1083

1595

2078

2334

30

VAR_CURRENTLIMIT

F

Y

R/W

Current limit

[A]mp

61

573

1085

1597

2079

2335

31

VAR_
PEAKCURRENTLIMIT16

F

Y

R/W

Peak current limit for 16kHz operation

[A]mp

63

575

1087

1599

2080

2336

32

VAR_PEAKCURRENTLIMIT

F

Y

R/W

Peak current limit for 8kHz operation

[A]mp

65

577

1089

1601

2081

2337

33

VAR_PWMFREQUENCY

W

Y

R/W

PWM frequency selection
0 - 16kHz; 1 - 8kHz

0 - 1

67

579

1091

1603

2082

2338

* These are all R/W variables but they only become active after variable 247 is set.