9400 regenerative power supply module | Parameter setting
Device interface
Automatic restart after power-on/trouble/fault
Auto-start option 0: auto-restart inhibited after power-on
If auto-start option 0 has been selected, the controller inhibit must be explicitly set after
power-on or after resetting a "Trouble" or "Fault" in order that the state of the regenerative
power supply module changes from "Device is ready to switch on" to "Device is switched
on". The subsequent change to the "Operation" state takes place when the controller is
enabled:
[4-13] State change when auto-restart is inhibited (C00142 = "0: Inhibited")
Pulses of the regenerative power supply module are inhibited
Pulses of the regenerative power supply module are enabled
With controller inhibit at power-on
Without controller inhibit at power-on
RFR
0
1
RFR
RFR
RFR
t
t
Initialisation
Switched on
Operation
Ready to switch on
Initialisation
Switched on
Operation
Ready to switch on