Parameter configuration, E-mail notification configuration – Rockwell Automation 281E ArmorStart EtherNet/IP - Getting Started User Manual
Page 20

20 ArmorStart EtherNet/IP Distributed Motor Controller Getting Started
Publication 280E-QS001B-EN-P – February 2011
Parameter Configuration
ArmorStart Ethernet/IP embedded web server provides the user the ability to
view and modify the device configuration without having to access RSLogix 5000.
To view the device configuration from the web server, select the Parameters
folder. For the parameter configuration, the user will login through the
Administrative Settings or when prompted.
E-mail Notification Configuration
ArmorStart Ethernet/IP internal web server will support the e-mailing of
warning and trip messages via Simple Mail Transfer Protocol (SMTP). The
configuration parameters for the SMTP Server’s IP address, user login, and port
number are configurable through the Administrative Settings page of the internal
web server. The user will configure the device name, device description, and
device trip type.
Figure 29 – E-mail Notification Configuration
E-mail triggers:
– When a trip occurs.
– When a trip is cleared.
– When a warning occurs.
– When a warning is cleared.
Note:
“Cleared Event” e-mails will only be sent when all events have been cleared
and if an trip event e-mail has previously been sent. For example, if the device is
configured to send e-mails when a phase loss trip is detected and an overload trip
is detected, no e-mail will be sent when the overload is cleared.