Control module led status and reset – Rockwell Automation 281E ArmorStart EtherNet/IP - Getting Started User Manual

Page 25

Advertising
background image

Publication 280E-QS001B-EN-P – February 2011

ArmorStart EtherNet/IP Distributed Motor Controller Getting Started 25

Refer to Parameter 63 "Base Trip" for the Base Module Trip Status.

Control Module LED
Status and Reset

The Control Module LED status and diagnostics consists of four status LEDs
and a Reset button. The following is a brief explanation of the operation of each
LED found on the Control Module.

The “Reset Button” is a local trip reset.

Table 5 - "Steady Red" MOD LED Status (Refer to Table 4 above.)

Fault Type

Description

0

EEPROM Fault

Non-volatile memory value out of range for a local parameter, or a write failure detected. This fault
is also reflected by a solid red MOD status LED.

1

Internal Comm2

The Internal communication connection has timed out. This fault is also reflected by a flashing red
MOD status LED.

2

Hardware Fault

Internal diagnostics checks failed. This fault is also reflected by a solid red MOD status LED.

3

Control Module An illegal or unsupported Control Module product code or revision has been detected. Also reported

if no Control Module is detected on power up. This fault is also reflected by a solid red MOD status
LED.

4…15

Reserved

Reserved

Table 6 - Network LED Status Indication

NET Status LED

Description

Recommended Action

Flashes
Green-Red-Off

The device has not completed the initialization, is
not on an active network, or may not be powered up.

Check to make sure the product is properly wired
and configured on the network.

Solid Green

The device is operating in a normal condition.

No action required.

Flashing Green

The device is operating in a normal condition.

No action required.

Flashing Red

Internal network fault has occurred.

Check 3-phase and control power connections.
Check ethernet connections.

Solid Red

The device has detected a major error that has
rendered it incapable of working.

Troubleshooting should be done to ensure that
the control module internal switch settings are
correct. Consult factory.

Figure 36 – LED Status
Indication and Reset

Table 7 - Control Module LED Status Indication

LED

Definition

Recommended Action

Power

This LED will be illuminated solid green
when switched control power is present
and with the proper polarity.

Ensure 24V DC is present on A1 and A2.
Check if the local disconnect is in the OFF
position.

Run

This LED will be illuminated solid green
when a start command and control power
is present.

Ensure 24V DC is present on A1 and A3.
Check if the user is properly commanding to
RUN via Instance 162 or 166.

Network This bicolor LED is used to indicate the

status of the internal network connection.

See Table 6, Network LED Status Indication
table above for additional information.

Fault

This LED is used to indicate the fault
status of the ArmorStart. When the unit is
faulted, the unit will respond with a
specific blink pattern to identify the fault.

See Table 8 and Table 9 below for
additional information.