Rockwell Automation 281E ArmorStart EtherNet/IP - Getting Started User Manual

Page 40

Advertising
background image

40 ArmorStart EtherNet/IP Distributed Motor Controller Getting Started

Publication 280E-QS001B-EN-P – February 2011

Table 19 - Instance 151

Produce Assembly - Instance 151 “Drive Status” - 284E Starters

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Reserve

Reserve

Reserve

Reserve

Reserve

Reserve

Reserve

Reserve

1

Reserve

Reserve

Reserve

Reserve

Reserve

Reserve

Reserve

Reserve

2

Reserve

Reserve

Reserve

Reserve

Reserve

Reserve

Reserve

Reserve

3

Reserve

Reserve

Reserve

Reserve

Reserve

Reserve

Reserve

Reserve

4

At

Reference

Net Ref

Status

Net Ctl

Status

Ready

Running

Rev

Running

Fwd

Warning Tripped

5

Contact2

Contact1

140M On

HOA

Input 4

Input 3

Input 2

Input 1

6

Output Frequency (Low) (xxx.x Hz)

7

Output Frequency (High) (xxx.x Hz)

8

Net Out 8

Net Out 7

Net Out 6 Net Out 5

Net Out 4

Net Out 3

Net Out 2 Net Out 1

9 Logic

Enable

Net Out

15

Net Out

14

Net Out

13

Net Out 12

Net Out 11

Net Out

10

Net Out 9

10

Value of the parameter pointed to by "Parameter 13 Prod Assy Word 0" (low byte)

11

Value of the parameter pointed to by "Parameter 13 Prod Assy Word 0" (high byte)

12

Value of the parameter pointed to by "Parameter 14 Prod Assy Word 1" (low byte)

13

Value of the parameter pointed to by "Parameter 14 Prod Assy Word 1" (high byte)

14

Value of the parameter pointed to by "Parameter 15 Prod Assy Word 2" (low byte)

15

Value of the parameter pointed to by "Parameter 15 Prod Assy Word 2" (high byte)

16

Value of the parameter pointed to by "Parameter 16 Prod Assy Word 3" (low byte)

17

Value of the parameter pointed to by "Parameter 16 Prod Assy Word 3" (high byte)

Figure 43 – Example of

RSLogix 5000 Command

Assembly Table

Table 20 - Instance 162

Consume Assembly - Instance 162 “Starter Cmd” - 280E/281E Starters

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Output B

Output A

Fault Reset

Run Rev

Run Fwd

1

Net in 7

Net in 6

Net in 5

Net in 4

Net in3

Net in 2

Net in 1

Net in 0

2

Net in 15

Net in 14

Net in 13

Net in 12

Net in 11

Net in 10

Net in 9

Net in 8

Table 21 - Instance 166

Consume Assembly - Instance 166 “Drive Cmd” – 284E Starters

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

User Out B

User Out A

Jog Rev

Jog Fwd

Fault Reset

Run Rev

Run Fwd

1

Drive In 4

Drive In 3

Drive In 2

Drive In 1

Decel

Control 2

Decel

Control 1

Accel

Control 2

Accel

Control 1

2

Comm Frequency Command (Low) (xxx.x Hz)

3

Comm Frequency Command (High) (xxx.x Hz)

4

Net in 8

Net in 7

Net in 6

Net in 5

Net in 4

Net in 3

Net in 2

Net in 1

5

Net in 16

Net in 15

Net in 14

Net in 13

Net in 12

Net in 11

Net in 10

Net in 9