44

Rockwell Automation Publication 10000337275 Ver 01—October 2014

Chapter 7

Application examples and connection diagrams

SafeZone Mini with restart interlock and external device monitoring

Fig. 43: Connection diagram for

SafeZone Mini with

restart interlock and

external device monitoring

SafeZone Mini in conjunction with relays/contactors; operating mode: with restart interlock (universal I/O 1 must be
configured as reset) and external device monitoring (universal I/O 2 must be configured as EDM).

SafeZone Mini in combination with a GSR SI safety relay

Fig. 44: Connection diagram for

SafeZone Mini in combination

with a GSR SI safety relay

SafeZone Mini in combination with a GSR SI safety relay: operating mode of SafeZone Mini is ON/OFF and GSR SI is
configured for monitored manual reset.

SafeZone Mini

Shld
wire

Brn

Yel***

Grn**

Blu

Gry

Pnk

Wht*

Color Pin Signal

Wht

1

Output - Warning Field1*

Brn

2

+24V DC

3

Universal I/O1** (Reset)

Yel

4

Universal I/O2*** (EDM)

Gry

5

OSSD 1

Pnk

6

OSSD 2

Blu

7

0V DC

Shld

8

Earth Ground

Reset

K1

K2

K1

K2

* Not configured for this application

*

No Connection

** Software Configured for Reset input

*** Software Configured for EDM

+24V DC

0V DC

L1

M

L2 L3

K1

K2

Grn

A2

A1

+

-

S11 S21 S12 S22

L11 Y32 S34 13

13

14

14

23

23

24

24

24VDC

IN1

SI

RESET 0

MM

AM

K2

Reset

K1

K2

M

24V DC

0V DC

Monitored Manual Reset

SafeZone Mini

Shld
wire

Brn

Yel*

Grn*

Blu

Gry Pnk

Wht*

Color

Wht

Brn

Grn

Yel

Gry

Pnk

Blu

Shld

Pin

1
2
3
4
5
6
7
8

Signal

Output-Warning Field1*
+24V DC
Universal I/O1*
Universal I/O2*
OSSD 1
OSSD 2
0V DC
Earth Ground

* not configured for this

application
no connection

L1 L2 L3

K1