Chapter 12

Technical specifications

How to calculate the total response time T

S

:

T

S

= t

B

+ T

MFA

+

Where …
t

B

= Basic response time = 80 ms

T

MFA

= Supplement due to multiple sampling > 2

Multiple sampling

On the SafeZone Mini at least double multiple sampling is always set. For a multiple sampling of three or higher you must
add a supplement of 80 ms to the basic response time.

Table 16: Supplements for multiple sampling

Timing behavior of the OSSDs
of the SafeZone Mini

The SafeZone Mini tests the OSSDs immediately after switch on and then at regular intervals. For this purpose the
SafeZone Mini briefly switches off both OSSDs (for 300

s) and checks whether the OSSDs switch to the OFF state during

this time.

Note

Ensure that the safety inputs on the controller used do not respond to these test pulses and as a result cause the machine
or system to unintentionally shutdown!

Fig. 50: Diagram of the test pulses at the OSSDs

Approximately 35 ms after the switch on of the OSSDs, the SafeZone Mini performs the first voltage test and then after a
half basic response time (40 ms) a second voltage test.

Multiple sampling

Supplement

Basic response time + supplement

2 times (basic setting)

0 ms

80 ms

3 times

40 ms

120 ms

4 times

80 ms

160 ms

5 times

120 ms

200 ms

6 times

160 ms

240 ms

7 times

200 ms

280 ms

8 times

240 ms

320 ms

9 times

280 ms

360 ms

10 times

320 ms

400 ms

11 times

360 ms

440 ms

12 times

400 ms

480 ms

13 times

440 ms

520 ms

14 times

480 ms

560 ms

15 times

520 ms

600 ms

16 times

560 ms

640 ms

Approx.
35 ms

40 ms

120 ms

120 ms

120 ms

OSSD1

OSSD2

t

t