Mechanical ratings, Altitude derating, Specifications (cont.) – Rockwell Automation 1503VC IntelliVAC Contactor Control Module User Manual

Page 10

Advertising
background image

1-6

Product Description

1503-UM051D-EN-P – June 2013

Table 1.B – Mechanical Ratings

Operating: 0° to 60°C ambient at the control module X

Temperature

Non-Operating: -40° to 85°C

Altitude

-1000 to 5000 meters

Pollution

Pollution level II (as defined by UL 840 and IEC 60664-1)

Humidity

Class II
Shock – 15 g peak, 11 milliseconds

Shock and
Vibration
(Operational)

Vibration – 10 to 57 Hz, 0.015 inch displacement peak to peak
- 57 to 150 Hz, 2.5 g acceleration

X

Ambient temperature is derated at altitudes above 1,000 meters (3,300 feet).

Please refer to Table 1.C.

Table 1.C – Altitude Derating

Altitude

DIP Switch Setting 1, 2, 3 X

Maximum Operating Ambient

at the control module (°C) Y

-1000 to 0

000

60

1 to 1000

001

60

1001 to 2000

010

58

2001 to 3000

011

56

3001 to 4000

100

54

4001 to 5000

101

52

X

Refer to Chapter 4.

Y

Derate by 2°C / 1000 m for high altitude operation

5.1 (0.20)

Dimensions in mm (inches)

29.7

(1.17)

174.8

(6.88)

185.3

(7.29)

59.4

(2.34)

165.9 (6.53)

5.8 (0.228)

2 places

5.1 (0.20)

Dimensions in mm (inches)

29.7

(1.17)

174.8

(6.88)

185.3

(7.29)

59.4

(2.34)

165.9 (6.53)

5.8 (0.228)

2 places

Figure 1.3 – Mechanical Dimensions

Specifications (cont.)

Advertising