Fuse protection, Grounding – Rockwell Automation 1503VC IntelliVAC Contactor Control Module User Manual

Page 18

Advertising
background image

3-6

Installation and Wiring

1503-UM051D-EN-P – June 2013

Fuse Protection

The IntelliVAC module requires external fuse protection to

coordinate with the power supply and contactor. The fuse ratings

shown in Table 3.A allow the passage of inrush currents expected

when the contactor is closed, or from recommended external

capacitors for the TDUV option. They will also protect the contactor

coils in the event of a module malfunction.

The recommended fuses have been tested to ensure reliable

protection of the module. If the supply voltage is DC, the module

must be used with an external fuse that is approved for and rated to

interrupt the DC voltage supply. The types listed are Ferraz-Shawmut

Midget Fuses (1-1/2" X 13/32"). The TRM is a time-delay type,

rated 250 VAC. The ATM is a fast-acting type, rated 500 VDC.

Table 3.A – IntelliVAC Fuse Protection

Recommended Fuse

Rated Supply Voltage

Contactor Type

(minimum)

(maximum)

400A EH

TRM 2

TRM 3.2

800A EH

TRM 2

TRM 6.25

110/120 VAC

400/800A ML

TRM 2

TRM 3.2

400A EH

TRM 2

TRM 6.25

800A EH

TRM 2

TRM 6.25

220/240 VAC

400/800A ML

TRM 2

TRM 6.25

400A EH/ML

ATM 3

ATM 3

125 VDC

800A EH/ML

ATM 5

ATM 6

400A EH/ML

ATM 3

ATM 5

250 VDC

800A EH/ML

ATM 5

ATM 6

EH = Electrically Held vacuum contactor

ML = Mechanically Latched vacuum contactor

Grounding

The IntelliVAC module must be connected to a common ground

terminal (PE) on the controller panel. The ground terminal is located

on top of the module enclosure for Series A design (refer to Figure

3.7), and on the bottom of module enclosure for Series B design,

(refer to Figure 3.6)

A T T E N T I O N

A T T E N T I O N

It is important that IntelliVAC is properly

grounded using the ground connection

provided. Failure to do so may result in

damage to equipment or personal injury.


Advertising